Technical Specifications
| AC Power | 29.9kW - 50kW |
|---|---|
| Inverter Type | All-in-one hybrid energy storage system |
| MPP Voltage Range | 180 – 850 Volt |
| MPP Tracker | 4 – 6 (model-dependent) |
| Phases | 3 |
| Communication | Wi-Fi, Ethernet, RS485 |
| Pieces per Package | 1 per carton, 1 per pallet |
| Warranty | 10 years |
Product Description
SAJ CHS2 30 – 50 kW All-in-One C&I ESS
A fully integrated, pre-installed energy storage solution for small commercial and industrial applications.
The CHS2 combines a 30–50 kW hybrid inverter with up to 100 kWh of LFP battery storage in a single, outdoor-rated IP55 cabinet.
With 200% DC oversizing, 6 MPPTs, and seamless generator integration, it delivers high revenue and ultimate safety with minimal on-site work.
Design
| Size (H×W×D) | 1980 × 988 × 1065 mm |
| Weight | 1035 – 1365 kg (depending on battery capacity) |
| Cooling | Air conditioner |
| Enclosure | IP55 (Cabinet), IP66 (Inverter) |
PV & AC Specs
| Rated AC Power | 30 kW / 50 kW |
| Max PV Power | 60 – 100 kWp DC (200%) |
| MPPTs / Strings | 4 × 2 (30 kW) / 6 × 2 (50 kW) |
| MPPT Range | 180 – 850 V |
| Max String Current | 22.5 A (45 A per MPPT) |
| Grid Output | 3L+N+PE, 380/400 V |
| UPS Backup | 30 kVA / 55 kVA |
| Eficiência máxima | 98.0 % |
Battery Specs
| Chemistry | LiFePO4 (280 Ah C&I cells) |
| Capacity | 57 / 72 / 86 / 100 kWh |
| Max Charge / Discharge | 140 A |
| Special Features | Cabinet-level fire protection, CO & smoke detection |
Smart Functions
- Intelligent scheduling for peak shaving & demand response
- Seamless diesel generator integration
- AC coupling ready for system retrofits
- Core health warning and advanced thermal management
- Wi-Fi / Ethernet / RS485 for VPP integration
Safety & Protection
- Standard AFCI to prevent DC arc faults
- Type II AC & DC surge protection
- Active anti-islanding, AC short-circuit & overload protection
- Complies with VDE4105, CEI 0-21, EN50549, AS4777.2, G99
Install & Service
- Fully pre-installed and debugged in the factory
- Ground-mounted cabinet for fast deployment
- Commission in minutes via eSAJ Home app
- Global SAJ service network
Warranty
| Standard Cover | 10 years |
Product Resources
Download the latest user manual & datasheet:
Product Video Showcase
Watch our product demonstrations and tutorials
Revolutionize Energy Storage Solutions with SAJ C&I Smart PV&ESS All-in-One Solution CHS2 series
Video failed to load
SAJ C&I Smart All-in-One Energy Storage Solution CHS2 - 2024 Featured Projects Spotlight
Video failed to load
SAJ CHS2 ALL-IN-ONE hybrid energy storage solution revolutionizes energy in Sweden's C&I Sector
Video failed to load
SAJ CHS2 Commercial Hybrid system 50KW+100kwh Training 20240129
Video failed to load
SAJ C&I Energy Storage System CHS2-P series Parallel Connection Installation Tutorial-2024 - EN
Video failed to load
SAJ CHS2 Demonstration on the rooftop
Video failed to load
How Condere Beat Unstable&Costly Power with SAJ’s CHS2 | Powering SA Manufacturing
Video failed to load
Related Articles
Explore more content related to this product
Application Scenarios
Discover how this product can be used in different real-world scenarios
The mid-sized facilities
Who it’s for: Small to medium-sized manufacturing plants, workshops, or agricultural facilities with heavy daytime machinery loads and a need for stable, high-quality power.
Typical loads & priorities (example):
| Load | Power (kW) | Energy Source Priority |
|---|---|---|
| CNC Machines / Welders | 20–40 | 1. Solar / 2. Grid |
| Lighting & HVAC | 5–15 | 1. Solar / 2. Battery / 3. Grid |
| Control Systems & Servers | 1–3 | UPS Backup (Solar/Battery) |
| Diesel Generator (DG) | Up to 50 | Backup for extended outages |
How it runs (Peak Shaving & Backup Mode):
Working Hours: PV → Power all loads; surplus → Charge Battery Evening Peak: Battery → Power essential loads (security, servers) Grid Outage: Battery → Instantly power backup circuits; DG can support/recharge
Sizing guide (for reference):
- A 50 kW / 100 kWh CHS2 system paired with a 100 kWp PV array can cover a significant portion of a factory’s daytime energy needs, saving thousands on electricity bills.
- The 100 kWh battery can provide over 3 hours of full 30 kW backup power, ensuring a safe shutdown or continued operation of critical processes.
“Our electricity bill was our biggest overhead. The CHS2 now covers most of our daytime power, and the backup function has already saved a production batch during a grid fault.”
Commercial Building & Office Park
Who it’s for: Multi-tenant office buildings, retail centers, or private schools that want to reduce common area energy costs, offer EV charging as an amenity, and provide tenants with reliable power.
Typical loads & priorities (example):
| Load | Power (kW) | Energy Source Priority |
|---|---|---|
| Central HVAC System | 15–30 | 1. Solar / 2. Grid |
| Office Lighting & Power | 10–20 | 1. Solar / 2. Battery / 3. Grid |
| Elevators & IT Infrastructure | 5–10 | UPS Backup (Solar/Battery) |
| EV Charging Stations | 22+ | Managed by EMS (Solar/Grid) |
How it runs (Time-of-Use & VPP Mode):
Daytime: PV → Power building loads; surplus → Charge Battery Evening: Battery → Power common areas/security; participate in VPP events Grid Outage: Battery → Instantly power backup circuits (IT, emergency lights)
Revenue guide (for reference):
- A 50 kW / 100 kWh system can significantly reduce a building’s demand charges by shaving peaks.
- By participating in Virtual Power Plant (VPP) programs, the stored energy can be sold back to the grid during high-demand events, creating a new revenue stream.
“The CHS2 was a smart investment. It lowered our operating costs and the VPP income is a welcome bonus. Our tenants appreciate the reliable power and green credentials.”
Remote Community & Off-Grid Resilience
Who it’s for: Remote communities, eco-resorts, or critical infrastructure sites with an unreliable grid connection or a complete off-grid requirement.
System components & roles (example):
| Component | Role |
|---|---|
| PV Array (e.g., 80 kWp) | Primary energy source; powers loads and charges battery |
| CHS2 Battery (e.g., 100 kWh) | Stores daytime energy for night use and cloudy days |
| Diesel Generator (e.g., 50 kW) | Backup source; recharges battery when solar is insufficient |
| Community Loads | Powered 24/7 by the microgrid |
How it runs (Off-Grid Mode):
Sunny Day: PV → Power loads; surplus → Charge Battery Night/Cloudy: Battery → Power loads Low Battery: CHS2 automatically starts DG → Power loads & recharge Battery Full Battery: CHS2 automatically stops DG to save fuel
Resilience guide (for reference):
- A 100 kWh battery can sustain a 10 kW average load for nearly 9 hours without any solar or DG input.
- The intelligent DG control can reduce generator runtime by over 80% compared to a traditional DG-only system, massively cutting fuel costs and emissions.
“We finally have reliable, 24-hour power. The CHS2 runs silently on solar and battery most of the time, and the generator only kicks in when absolutely needed. It’s a game-changer for us.”
How We Work With You
From your first call to final delivery, we make the process simple and clear
Talk & Plan
We listen to your needs and create a plan that works for you. Our team will help you understand all your options.
Quote & Agree
You get a clear price with no hidden costs. Once you're happy with everything, we sign the agreement and start working.
Make & Check
We carefully make your order and check everything meets our high standards. You'll know exactly how things are going.
Ship & Support
Your order ships safely to you on time. We're always here to help if you need anything after delivery.
Frequently Asked Questions
Find answers to common questions about our products and services
What is CHS2 (30–50 kW) and why do installers choose it for small C&I?
At a glance
- All-in-one cabinet: three-phase hybrid inverter + high-voltage LFP battery + BMS + AC/DC protection.
- Power classes: 30 kW (T4, 4 MPPT) and 50 kW (T6, 6 MPPT).
- Battery options (usable): 51.5 / 64.4 / 77.3 / 90.2 kWh.
- PV side: up to 60 kWp (30 kW) or 100 kWp (50 kW), 180–850 V MPPT, 1000 V max.
Design choices that reduce site time
- Factory-integrated wiring, DC/AC Type II SPD, AFCI, anti-islanding (AFD).
- 6 MPPT option and 22.5 A string current — pairs well with 210-cell high-power modules.
- DG (diesel generator) input and dry-contact control built in.
- Cabinet IP55 with active cooling; inverter section IP66.
| Model | MPPT | PV @ STC | Usable battery (kWh) | Cooling / Ingress |
|---|---|---|---|---|
| CHS2-30K-T4-X | 4 | 60 kWp | 51.5–90.2 | Air-conditioned / IP55 (cabinet), IP66 (inverter) |
| CHS2-50K-T6-X | 6 | 100 kWp | 51.5–90.2 | Air-conditioned / IP55 (cabinet), IP66 (inverter) |
How do I plan PV strings and battery size for CHS2?
- Voltage window: 180–850 V MPPT; 1000 V max.
- Per-string current: up to ~22.5 A (supports high-current 210-cell modules).
- Strings per MPPT: 2; balance strings by irradiance and length.
| Pack option | Usable (kWh) | Modules | Charge/Discharge (A) |
|---|---|---|---|
| CB2-57.3-HV5 | 51.5 | 4 | 140 |
| CB2-71.6-HV5 | 64.4 | 5 | 140 |
| CB2-85.9-HV5 | 77.3 | 6 | 140 |
| CB2-100.3-HV5 | 90.2 | 7 | 140 |
Runtime math (simple)
Runtime (h) ≈ Usable battery (kWh) ÷ Load (kW)- 64.4 kWh usable → ~3.2 h at 20 kW essential load.
- 90.2 kWh usable → ~4.5 h at 20 kW; ~1.6 h at 55 kVA peak is not continuous.
What protections and safety layers are built in?
| Layer | What it does |
|---|---|
| AFCI (PV arc-fault) | Cuts DC side on arc signature to reduce fire risk. |
| Type II SPD (DC/AC) | Limits surge energy from lightning or switching events. |
| AFD anti-islanding | Stops feeding a dead grid during outages. |
| RCMU | Residual-current monitoring for leakage detection. |
| Cabinet sensors | CO/smoke/temperature/humidity/water sensors; triggers alarms and protection. |
Everyday effect
- Backup output THDv < 3% for sensitive IT/POS loads.
- 100% three-phase voltage imbalance tolerance on backup.
- Emergency stop and 12 V output available for fast-shutdown accessories.
What backup power can CHS2 deliver, and can I use a diesel generator?
| Model | Backup apparent power | 5-s surge | Voltage / Freq | THDv |
|---|---|---|---|---|
| 30K-T4-X | 33 kVA | 45 kVA | 3L+N+PE, 380/400 V; 50/60 Hz | <3% |
| 50K-T6-X | 55 kVA | 75 kVA | 3L+N+PE, 380/400 V; 50/60 Hz | <3% |
Runtime shortcut
Runtime (h) ≈ Usable battery (kWh) ÷ Average load (kW) 51.5 kWh usable → ~2.6 h @ 20 kW 90.2 kWh usable → ~4.5 h @ 20 kW
Generator use
- Dedicated GEN input (3L+N+PE, 380/400 V; 50/60 Hz).
- Start/stop dry contact available; set timing in control menu.
- Match generator kVA to backup load + charging current; allow margin for motor inrush.
What does commissioning and monitoring look like on CHS2?
- LAN, RS485 (meter/parallel), CAN (BMS/EMS), dedicated EMS, RCR/DRM inputs.
- Meter (RS485) for import/export control; CT orientation arrow toward inverter.
- Wi-Fi/Ethernet/4G module slot for cloud.
- Power on DC/AC and main switch; check front LEDs.
- Use eSAJ Home App (BLE → Wi-Fi/Ethernet/4G) to bind and set grid code.
- Verify meter RS485 A/B and CTs; confirm live data and phase order.
- Export/generation limit via app.
- RCR/DRM inputs for dispatch (e.g., Germany/AU requirements).
- Fixed PF / Volt-Var / Volt-Watt modes as per local code.
What does Sunriver Electric include to make CHS2 projects easier to quote and deliver?
- LAN, RS485 (meter/parallel), CAN (BMS/EMS), dedicated EMS, RCR/DRM inputs.
- Meter (RS485) for import/export control; CT orientation arrow toward inverter.
- Wi-Fi/Ethernet/4G module slot for cloud.
- Power on DC/AC and main switch; check front LEDs.
- Use eSAJ Home App (BLE → Wi-Fi/Ethernet/4G) to bind and set grid code.
- Verify meter RS485 A/B and CTs; confirm live data and phase order.
- Export/generation limit via app.
- RCR/DRM inputs for dispatch (e.g., Germany/AU requirements).
- Fixed PF / Volt-Var / Volt-Watt modes as per local code.
Still have questions?
Can't find the answer you're looking for? Our support team is here to help you.
Related Products
Discover similar products that might interest you
Ready to Talk About This Product?
Tell us what you need—from pricing and availability to technical specs or project planning. Our product team will respond within 24 hours.
- Request tailored quotations and lead times
- Get engineering support and compatibility checks
- Receive product literature and case studies
Obrigado! Recebemos a sua consulta.
Our product specialists will reach out within 24 hours. A detailed Thank You page has opened in a new tab.